Component Function Check
AIR MIX DOOR MOTOR
WITHOUT LEFT AND RIGHT VENTILATION TEMPERATURE SEPARATELY CONTROL SYSTEM : Component Function Check
1. CONFIRM SYMPTOM BY PERFORMING THE FOLLOWING OPERATIONAL CHECK
1.Turn temperature control dial clockwise until 32�C (90�F) is displayed.
2.Check for warm air at discharge air outlets.
3.Turn temperature control dial counterclockwise until 18�C (64�F) is displayed.
4.Check for cool air at discharge air outlets.
Is the inspection result normal?
YES- INSPECTION END
NO- Go to diagnosis procedure. Diagnosis Procedure.